Short answer: All four Dragino nodes below are battery-powered LoRaWAN sensors on the US915 band. Pick by what you need to read: PS-LB (from $286.99) for liquid level with an immersion probe, RS485-LB ($134.99) to put an existing Modbus RTU / RS485 instrument on LoRaWAN, LHT65N-DC ($100.99) for a dry-contact status or pulse count plus panel temperature and humidity, and D20-LB ($139.99) for one temperature point on a waterproof probe. Every node needs a LoRaWAN gateway and network server, such as the RAK WisGate Edge Lite 2 (RAK7268V2) ($232.99). The specs below are taken from the product listings on this site.
Side-by-side specs
| PS-LB (immersion) | RS485-LB | LHT65N-DC | D20-LB | |
|---|---|---|---|---|
| What it reads | Liquid level / pressure from a stainless immersion probe | Any RS485 device you poll with Modbus or user-defined commands | Dry contact (open/closed, pulse count, open alarm) + built-in temperature and humidity | Temperature from a waterproof DS18B20 probe |
| Inputs / interfaces | 0-20 mA (0.02 mA accuracy), 0-30 V (0.02 V accuracy) | 1 x RS485, 1 x UART (3.3 V or 5 V), 1 x interrupt / digital I/O, 1 x I2C, 1 x one-wire | 3-wire external lead (VCC / GND / INT), 1 m cable | External probe, -55 to 125 °C, ±0.5 °C (max ±2.0 °C) |
| Cable / probe options | 5, 10, 15 or 20 m | — | 1 m lead | Probe on cable |
| Battery (non-rechargeable) | 8500 mAh Li-SOCl2 | 8500 mAh Li-SOCl2 | 2400 mAh, built in | 8500 mAh Li-SOCl2 |
| Battery life (supplier figure) | Up to 5 years | Depends on interval and sensor load | More than 10 years | Up to 5 years |
| Node operating temperature | -40 to 85 °C | -40 to 85 °C | -40 to 80 °C (sensor range) | -40 to 85 °C |
| Enclosure | — | IP67 | Wall mount | — |
| Setup | BLE, wireless OTA | BLE v5.1, AT commands, LoRaWAN downlink, OTA | AT commands, program port | BLE, wireless OTA |
| Band | US915 | US915 | US915 | US915 |
| Price | $286.99 (5 m) to $351.99 (20 m) | $134.99 | $100.99 | $139.99 |
| Product page | PS-LB | RS485-LB | LHT65N-DC | D20-LB |
Which one do I need?
I need a tank, pit or sump level at a site with no power or conduit
The PS-LB immersion version. The probe sits at the bottom of the tank and the node sends the reading over LoRaWAN. The listing does not state the probe’s measuring range, so confirm the range for your tank depth before you order.
I already have a Modbus RTU meter or totalizer and no cable back to the RTU
The RS485-LB. It polls the RS485 device on a schedule, builds a payload from the reply and uploads it. It can also power the connected sensor from its controllable 3.3 V / 5 V output.
I need to know if a pump, compressor or heater is running, or if a panel door is open
The LHT65N-DC on a voltage-free (dry) auxiliary contact. It also logs panel temperature and humidity from its built-in sensor.
I need a freeze watch on a water line or a pump house
The D20-LB. The probe reads -55 to 125 °C; keep the node body itself within -40 to 85 °C.
FAQ
Do these sensors work without a gateway?
No. Every node needs a LoRaWAN gateway and a network server (not included). The RAK7268V2 is an 8-channel US915 gateway with Ethernet and Wi-Fi (optional LTE) and an MQTT bridge to network servers such as ChirpStack. It has an indoor enclosure: on a field site, install it in a weather-protected panel or building.
Can I use them outside the United States?
All four are listed on the US915 band. Ask before ordering for another country.
Can I use them for control or shutdown?
No. LoRaWAN is a low-data-rate link for periodic readings. These nodes are for monitoring only, not for control or safety functions. No hazardous-area approval or certificate document is supplied; install them in non-classified locations.
How do I see the readings on my phone?
Your network server receives the readings. If it publishes the decoded readings over MQTT, AutomationBotX Cloud can display them: its agent on a Raspberry Pi or plant PC reads Modbus TCP or MQTT, read-only, and shows values with alarms in the app. It is monitoring only and never sends commands to the equipment. The first 10 machines are free, no card required.
Can I get a volume price for a project?