WS1528 Frequency to 4-20 mA / RS485 Transmitter – 0-100 Hz to 0-10 kHz Input, 0.2 % Accuracy, DIN Rail
Price range: $76.99 through $95.99
DIN-rail transmitter that converts a frequency or pulse signal into 4-20 mA or RS485. Choose the input range (0-100 Hz up to 0-10 kHz) and the output. 0.2 % accuracy class per supplier.
Request a quote / bulk pricing
Buying for a business or need several units? Send us the quantity and destination and we will reply with a quote.
Technical specification sheet · automationbotx.com
| SKU | ABX-AE-389803 |
|---|---|
| Manufacturer part number | WS1528 |
| Input Range (options) | 0-100 Hz · 0-500 Hz · 0-1 kHz · 0-5 kHz · 0-10 kHz |
| Output (options) | 4-20 mA · RS485 |
| Typical uses | turbine meter flow rate into an analog input, engine or pump speed from a magnetic pickup, and conveyor or shaft speed monitoring. |
| Brand | Qidian Auto |
| Model | WS1528 |
| Input | Frequency signal |
| Input range | 0-100 Hz / 0-500 Hz / 0-1 kHz / 0-5 kHz / 0-10 kHz (options) |
| Output | 4-20 mA or RS485 (options) |
| Accuracy class | 0.2 % |
| Operating temperature | -20 to 60 °C |
| Mounting | 35 mm DIN rail |
| Display | None (analog unit) |
Data as published in this listing by the manufacturer or supplier. Price, stock and shipping are shown above.
Ask about this product
Compatibility, wiring, a value that is missing? Send your question and we reply by email. Prefer to call? +1 346 283 9580.
Description
Turbine flow meters, magnetic pickups (MPU) and other pulse-output sensors give a frequency, while most RTUs and PLC analog cards want 4-20 mA or a Modbus value. The WS1528 sits on a 35 mm DIN rail and converts a frequency input into a 4-20 mA output or an RS485 output, so a pulse signal can be trended and alarmed like any other analog point.
Typical uses: turbine meter flow rate into an analog input, engine or pump speed from a magnetic pickup, and conveyor or shaft speed monitoring.
Specifications (as listed by the supplier)
- Brand: Qidian Auto
- Model: WS1528
- Input: Frequency signal
- Input range: 0-100 Hz / 0-500 Hz / 0-1 kHz / 0-5 kHz / 0-10 kHz (options)
- Output: 4-20 mA or RS485 (options)
- Accuracy class: 0.2 %
- Operating temperature: -20 to 60 °C
- Mounting: 35 mm DIN rail
- Display: None (analog unit)
Notes
- Pick the input range closest to your maximum signal frequency for best resolution.
- Not rated for hazardous areas per the supplier listing; mount in a safe-area panel.
Additional information
| Input Range | 0-100 Hz, 0-500 Hz, 0-1 kHz, 0-5 kHz, 0-10 kHz |
|---|---|
| Output | 4-20 mA, RS485 |









Reviews
There are no reviews yet.