Temperature Measurement in a Panel: PT100, 4-20 mA Transmitter, RS485 or PID — Which Part Do You Need?

Short answer: A temperature point in a panel is a chain of parts. A sensor touches the process (PT100 RTD or K thermocouple). A transmitter turns the reading into a signal your PLC or RTU understands (4-20 mA or RS485 Modbus). A controller acts on it (for example a PID that switches a heater). Buy only the part you are missing. The four parts below are in stock at AutomationBotX, with specs taken from their listings.

Which part do I need?

You have…You need…PartPrice (USD)
A PLC analog input and no sensor yetA PT100 probe plus a 4-20 mA transmitterWZP-PT100 probe + DIN-rail PT100 transmitterfrom $6.01 + $32.99
A PT100 already installed, but the PLC only reads 4-20 mAA PT100 transmitterDIN-rail PT100 transmitter$32.99
An RS485 Modbus network and a room or shelter to watchA Modbus temperature and humidity transmitterCWT-XYTH RS485 transmitterfrom $49.99
An electric heater to hold at a set temperature, no PLCA standalone PID controller with SSR and probePID controller kit (K thermocouple, 40 A SSR)$43.99

Prices as listed on 5 November 2026; the product page always shows the current price for each variant.

The four parts, side by side

WZP-PT100 probePT100 transmitterCWT-XYTH RS485PID controller kit
Store SKUABX-0634ABX-AE-008861ABX-AE-350305ABX-AE-952234
RoleSensorTransmitter (PT100 in, 4-20 mA out)Sensor + transmitter (RS485 out)Controller + SSR + probe
Sensing elementPT100 RTDTakes a PT100 inputBuilt-in temperature and humidityK-type thermocouple
Range-20 to 450 °C in the listing’s parameters (the same listing also states -200 to 600 °C as measurement range)Choose a span from 0-50 °C up to 0-500 °C, or -50 to 50/100/150/200 °C-40 to 125 °C, 0-100 % RH0-400 °C
OutputResistance (to a transmitter or controller)4-20 mARS485 Modbus RTU (default 9600 8N1, address 1)SSR drive to a 40 A SSR (load 24-380 VAC)
Supplyn/a24 VDC12-24 VDC100-240 VAC
MountingØ4 x 30 mm tube, 0.5 m cableDIN railWall or 35 mm DIN rail48 x 96 mm panel cut-out

Questions and answers

PT100 or K thermocouple?

Both appear above. A PT100 is a resistance sensor and needs a PT100 input or a PT100 transmitter. A K thermocouple produces a small voltage and needs a thermocouple input, like the one on the PID controller in the kit. Do not mix them: a PT100 transmitter cannot read a thermocouple.

How do I choose the transmitter range?

Pick the narrowest span that still covers your highest and lowest expected temperatures. The 4-20 mA signal is spread over that span, so a tighter span gives your PLC finer steps.

How does the PLC scale the RS485 transmitter?

Per the listing, the temperature register reads 0-1650 for -40 to 125 °C, and the humidity register reads 0-1000 for 0-100 % RH.

Can I use these in a hazardous area?

None of these listings includes a hazardous-area certificate. Mount them in a safe-area panel or shelter, and confirm what your site requires before you order.