Flow Switch Selection Guide: Reed vs Paddle vs Thermal Dispersion
Short answer: a flow switch answers one question: is liquid (or air) actually moving in this pipe? It gives an on/off contact, not a flow rate. Three designs cover most jobs. A reed / magnetic piston switch is compact and trips at a low, defined start flow on small lines. A paddle switch is the low-cost choice for larger pipes and pump protection. A thermal dispersion switch has no moving parts, works in water, oil and air, and gives an adjustable set point on 24 VDC. Pick by medium, then pipe size and thread, then the contact rating your circuit needs. Find it by part number. Buy it with the specs in front of you.
Specs at a glance: flow switches in stock
| Product | Principle | Connection | Trip point (as listed) | Contact / output | Pressure / temperature | Price |
|---|---|---|---|---|---|---|
| USM-FS21TS reed flow switch | Magnetic float + sealed reed, SUS304 body | 1/2″ NPT or 1/2″ BSPP | Closes at about 1.5 L/min; max flow 12 L/min (at 0.1 MPa) | Normally open, 10 W, 200 VDC, 0.3 A max | 0-60 °C | $51.99 |
| SKB inline flow switch | Inline magnetic switch, 304 stainless | DN15 or DN20 (thread type not stated by the supplier) | ≥5 L/min (DN15), ≥7 L/min (DN20) | Passive, normally open, 24 V AC/DC, 0.3 A | 0.05-1.6 MPa; -20 to 120 °C; IP65 | $79.99 |
| Stainless paddle flow switch HFS-SS | Paddle in a tee, ABS switch housing | G1/2, G3/4 or G1 (by model) | Set by paddle; 3-5 paddles supplied, trimmed to pipe size | SPDT, 3.5 A at 125 VAC / 2.5 A at 250 VAC | 10 bar; 0-100 °C | $36.99 |
| W20 paddle flow switch | Six-point baffle, magnetic sensing | See listing | Not stated in the listing | Not stated in the listing | Not stated in the listing | $26.99 |
| Thermal flow switch 24 VDC | Thermal dispersion (calorimetric), no moving parts | G1/2″, probe length by version; M12 connector | Adjustable: water 1-150 cm/s, oil 3-300 cm/s, air 20-2000 cm/s | Relay, 1 A at 48 VAC/DC; 6-LED flow bar | Up to 100 bar; medium -20 to 90 °C; IP67 | $183.99 |
Questions buyers ask
Flow switch or flow meter: which one do I need?
Use a flow switch when you only need to know “flow / no flow” to stop a pump, interlock a chiller or raise an alarm. Use a flow meter when you need the rate or the total (L/min, gallons, barrels). For meters, see our flow meter comparison.
Which type for pump dry-run protection?
On small lines up to 1/2″ with low flow, the USM-FS21TS reed switch trips at a defined start flow of about 1.5 L/min. On 1/2″ to 1″ lines with normal pump flow, a paddle switch is the lowest-cost option. If the liquid carries particles, or you want to set the trip point on site, the thermal switch has no paddle or float to jam.
Can I wire the switch straight to the pump motor?
No. The reed and SKB switches are rated 0.3 A, and the thermal switch relay 1 A at 48 V. Even the paddle switch (3.5 A at 125 VAC) should drive a relay, contactor coil or PLC input, not a motor directly.
NPT or BSPP?
US pipe is usually NPT. The USM-FS21TS is offered in both 1/2″ NPT and 1/2″ BSPP, so choose the variant that matches your fitting. The paddle and thermal switches use G (BSPP) threads; use a proper adapter on an NPT line. The SKB listing does not state the thread type.
Does a flow switch work on oil or compressed air?
The thermal switch lists separate setting ranges for water, oil and air. The SKB lists water, gas and oil as media. The reed and paddle switches are described for water lines.
How should I install it?
Follow the arrow on the body. The supplier of the USM-FS21TS asks for a strainer upstream and no strong magnetic fields or heavy vibration. The SKB is installed cable-up on horizontal pipe and inlet-down on vertical pipe. The thermal switch needs about 8 s to initialize after power-up and responds in 1-13 s (typical 2 s), so do not expect an instant trip.
Can I use these switches as a safety device?
No. None of these switches carries a third-party certification or SIL rating, and the W20 supplier calls the housing explosion-proof without a certificate. Do not use them in classified hazardous areas or as the only protection in a safety system. Use them for process monitoring and equipment interlocks.
See a no-flow event before it becomes a failed pump
A dry contact from a flow switch can go into a PLC input or a Modbus I/O module, and from there to a dashboard. AutomationBotX Cloud reads monitoring data only (it never controls your equipment and is not a safety system) and lists possible causes for a qualified technician to check. Free for up to 10 machines, no card needed. For signal options, see our RS485 / Modbus gateway guide and how remote monitoring works.